Buy Fluke i2500-10 iFlex® Flexible Current Probes

Buy Fluke i2500-10 iFlex® Flexible Current Probes
Buy Fluke i2500-10 iFlex® Flexible Current Probes Buy Fluke i2500-10 iFlex® Flexible Current Probes Buy Fluke i2500-10 iFlex® Flexible Current Probes
Brand: Fluke
Product Code: FLUi2500-10
Availability: 2 - 3 Days
Price: $225.50
Ex GST: $205.00
Qty:
  - OR -   Add to Wish List
Add to Compare

Unprecedented measurement flexibility

The iFlex flexible current probe (included) expands the measurement range to 2500 A ac while providing increased display flexibility, ability to measure awkward sized conductors and improved wire access.

Be ready for anything.

The Fluke iFlex flexible current probes expand the measurement range of the select Fluke meters to 2500 A ac while providing the ultimate measurement flexibility. The iFlex probes connect directly to the meter, displaying current measurements without error prone scaling factors. The 1.8 m (6 ft) cord allows separation between the measurement location and the clamp meter making it easier to view the display. The large loop size and thin cross section allow measurement of awkward sized conductors and improved wire access in crowded spaces. Available in 25 cm (10 in) and 45 cm (18 in) sizes.

Safety Conformance
IEC/EN 61010-1:2001, 1000V CAT III, 600V CAT IV

Features and benefits

  • Expands the measurement range to 2500 A ac while providing increased display flexibility, ability to measure awkward sized conductors and improved wire access
  • CAT IV 600 V, CAT III 1000 V
  • 7.5 mm coil diameter allows measurement in tight spaces
  • Ergonomic design allows easy operation with one hand
  • 1.8 m (6 ft) cable
  • Three-year warranty


How-to open the i2500-18 and i2500-10 iFlex flexible current probes:

Twist to unlock Pull to open


Safety Conformance
IEC/EN 61010-1:2001, 1000V CAT III, 600V CAT IV

Specifications

i2500-18 and i2500-10

Range

Resolution

Accuracy

AC Current*

2500 A

0.1 A

3% ± 5 digits**

Frequency*

500 Hz

0.1 Hz

0.5% ± 5 digits

External magnetic
field rejection

(with cable >10 cm from the coupling)

40 dB

Inrush*

 •

Safety rating

CAT III 1000 V, CAT IV 600 V

*When used with compatible Fluke meter. Accuracy stated includes probe and meter accuracy.
** For position accuracy at non-optimum positions, see Position sensitivity specifications table “A

 

Position sensitivity specifications

Distance from optimum

i2500-10

i2500-18

Additional iFlex error

A

0.5 in (12.7 mm)

1.4 in (35.6 mm)

± 0.5%

B

0.8 in (20.3 mm)

2.0 in (50.8 mm)

± 1.0%

C

1.4 in (35.6 mm)

2.5 in (63.5 mm)

± 2.0%


Measurement uncertainty assumes centralized primary conductor at optimum position, no external electrical or magnetic field, and within operating temperature.