A solid, basic installation tester.
The Fluke 1662 gives you Fluke reliability, simple operation and all the testing power you need for day-in, day-out installation testing.
Includes:
The 1662 puts more power in your hands by quickly and efficiently testing to all local regulations, protecting appliances that may be inadvertently connected to the system under test, and making it easy to share test results over your smartphone.
Measurement functions
Other features
Included accessories
AC voltage measurement | ||
Range | 500 V | |
Resolution | 0.1 V | |
Accuracy 45 Hz – 66 Hz | 0.8% + 3 | |
Input impedance | 360 kΩ | |
Overload protection | 660 V rms | |
Continuity testing (RLO) | ||
Range (autoranging) | 20 Ω / 200 Ω / 2000 Ω | |
Resolution | 0.01 Ω / 0.1 Ω / 1 Ω | |
Open Circuit Voltage | >4 V | |
Insulation resistance measurement (RISO) | ||
Test voltages | 100-250-500-1000 V | |
Accuracy of tTest voltage (at rated test current) | +10%, -0% | |
Test voltage | 50 V 100 V 250 V 500 V 1000 V |
|
Insulation resistance range | 20 MΩ /50 MΩ 20 MΩ / 100 MΩ 20 MΩ / 200 MΩ 20 MΩ / 200 MΩ / 500 MΩ 20 MΩ / 200 MΩ / 1000 MΩ |
|
Resolution | 0.01 MΩ / 0.1 MΩ 0.01 MΩ / 0.1 MΩ 0.01 MΩ / 0.1 MΩ 0.01 MΩ / 0.1 MΩ / 1 MΩ 0.01 MΩ / 0.1 MΩ / 1 MΩ |
|
Test current | 1 mA @ 50 kΩ 1 mA @ 100 kΩ 1 mA @ 250 kΩ 1 mA @ 500 kΩ 1 mA @ 1 MΩ |
|
Loop and line impedance (ZI) | ||
Range | 10 Ω / 0.001 Ω / High current mΩ mode | |
Resolution | 0.01 Ω / 0.1 Ω / 1 Ω | |
Prospective earth fault current, PSC test | ||
Range | 1000 A / 10 kA (50 kA) | |
Resolution | 1 A / 0.1 kA | |
Computation | Prospective earth fault current (PEFC) or Prospective short circuit current (PSC) determined by dividing measured mains voltage by measured loop (L-PE) resistance or line (L-N) resistance, respectively. | |
RCD testing, RCD types tested | ||
RCD Type | AC¹ G²,S³ |
|
Model 1662 | A4, AC¹, G²,S³ | |
Notes | ¹Responds to AC ²General, no delay ³Time delay 4Responds to pulsed signal 5Responds to smooth DC signal |
|
Tripping speed test (ΔT) | ||
Current settings¹ | 10-30-100-300-500-1000 mA – VAR 10-30-100 mA |
|
Multiplier | x ½, x 1 x 5 |
|
Measurement range | RCD Type G | 310 ms 50 ms |
RCD Type S | 510 ms 160 ms |
|
Notes | ¹1000 mA type AC only 700 mA maximum type A in VAR mode VAR mode not available for type B. |
|
RCD/FI-Tripping Current Measurement/Ramp Test (IΔN) | ||
Current range | 30% to 110% of RCD rated current¹ | |
Step size | 10% of IΔN² | |
Dwell time | Type G | 300 ms/step |
Type S | 500 ms/step | |
Measurement accuracy | ±5% | |
Specified trip current ranges (EN 61008-1) | 50% to 100% for Type AC 35% to 140% for Type A (>10 mA) 35% to 200% for Type A (≤10 mA) 50% to 200% for Type B ²5% for Type B |
|
Notes | ¹30% to 150% for Type A IΔN > 10 mA 30% to 210% for Type A IΔN = 10 mA 20% to 210% for Type B |
|
Phase Sequence Indication | ||
Icon | ![]() |
|
General Specifications | ||
Size (L x W x H) | 10 x 25 x 12.5 cm | |
Weight (incl. batteries) | 1.3 Kg | |
Battery size, quantity | Type AA, 6 ea. | |
Sealing | IP-40 | |
Safety | Complies with EN61010-1 Ed 2.0 (2001-02), UL61010, ANSI/ISA –s82.02.01 2000 and CAN/CSA c22.2 No. 1010 2nd edition | |
Overvoltage | CAT III / 500V; CAT IV 300V | |
Performance | EN61557-1 to EN61557-7 Second Edition and EN61557-10 Second Edition |
|